Hardware
The GPM PPC is composed normally by two hardware units, but this is not the only solution, other configurations may be applied.
In fact, the GPM PPC needs all the other RTUs in the field:
UNIT 1 | UC-8112 | Power Plant Controller |
UNIT 2 | UC-8112 | RTU SMB and other connection/adaptation SW, like SMB, Cap Banks |
All the Field RTUs | UC-8112 | Running Moxa process inside. |
- The PPC can also be commanded using PV+ but a windows machine is needed anyway to configure it.
-
The PPC UNIT Runs the Algorithm. Closed loop and PI controller.
-
The RTU Smart Bridge Unit adapts the Setpoints (P and Q orders) to the inverters.
-
The Cap Banks SW adapts also how the Capacitor banks need to be commanded.
-
The Configuration of the RTU SMB allows the SW "know" the Number of Inverters and "where" they are.
The RTU SMB sends a UDP message inside the LAN of the plant. This means that all the devices in the plant will receive this message (the infield IA240/ UC-8112). They will transmit this order to the inverter using Modbus RTU/TCP.